SE535935C2 - Device at a ventilation unit - Google Patents
Device at a ventilation unit Download PDFInfo
- Publication number
- SE535935C2 SE535935C2 SE1100319A SE1100319A SE535935C2 SE 535935 C2 SE535935 C2 SE 535935C2 SE 1100319 A SE1100319 A SE 1100319A SE 1100319 A SE1100319 A SE 1100319A SE 535935 C2 SE535935 C2 SE 535935C2
- Authority
- SE
- Sweden
- Prior art keywords
- nozzles
- holes
- air
- ventilation
- pressure
- Prior art date
Links
- 238000009423 ventilation Methods 0.000 title claims description 55
- 238000005192 partition Methods 0.000 claims description 4
- 230000009969 flowable effect Effects 0.000 claims 1
- 238000010276 construction Methods 0.000 description 2
- 238000005265 energy consumption Methods 0.000 description 2
- 230000007423 decrease Effects 0.000 description 1
- 239000002184 metal Substances 0.000 description 1
- 238000005293 physical law Methods 0.000 description 1
- XLYOFNOQVPJJNP-UHFFFAOYSA-N water Substances O XLYOFNOQVPJJNP-UHFFFAOYSA-N 0.000 description 1
Classifications
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F24—HEATING; RANGES; VENTILATING
- F24F—AIR-CONDITIONING; AIR-HUMIDIFICATION; VENTILATION; USE OF AIR CURRENTS FOR SCREENING
- F24F1/00—Room units for air-conditioning, e.g. separate or self-contained units or units receiving primary air from a central station
- F24F1/01—Room units for air-conditioning, e.g. separate or self-contained units or units receiving primary air from a central station in which secondary air is induced by injector action of the primary air
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F24—HEATING; RANGES; VENTILATING
- F24F—AIR-CONDITIONING; AIR-HUMIDIFICATION; VENTILATION; USE OF AIR CURRENTS FOR SCREENING
- F24F7/00—Ventilation
- F24F7/007—Ventilation with forced flow
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F24—HEATING; RANGES; VENTILATING
- F24F—AIR-CONDITIONING; AIR-HUMIDIFICATION; VENTILATION; USE OF AIR CURRENTS FOR SCREENING
- F24F1/00—Room units for air-conditioning, e.g. separate or self-contained units or units receiving primary air from a central station
- F24F1/0007—Indoor units, e.g. fan coil units
- F24F1/0043—Indoor units, e.g. fan coil units characterised by mounting arrangements
- F24F1/005—Indoor units, e.g. fan coil units characterised by mounting arrangements mounted on the floor; standing on the floor
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F24—HEATING; RANGES; VENTILATING
- F24F—AIR-CONDITIONING; AIR-HUMIDIFICATION; VENTILATION; USE OF AIR CURRENTS FOR SCREENING
- F24F11/00—Control or safety arrangements
- F24F11/70—Control systems characterised by their outputs; Constructional details thereof
- F24F11/72—Control systems characterised by their outputs; Constructional details thereof for controlling the supply of treated air, e.g. its pressure
- F24F11/74—Control systems characterised by their outputs; Constructional details thereof for controlling the supply of treated air, e.g. its pressure for controlling air flow rate or air velocity
- F24F11/77—Control systems characterised by their outputs; Constructional details thereof for controlling the supply of treated air, e.g. its pressure for controlling air flow rate or air velocity by controlling the speed of ventilators
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F24—HEATING; RANGES; VENTILATING
- F24F—AIR-CONDITIONING; AIR-HUMIDIFICATION; VENTILATION; USE OF AIR CURRENTS FOR SCREENING
- F24F13/00—Details common to, or for air-conditioning, air-humidification, ventilation or use of air currents for screening
- F24F13/02—Ducting arrangements
- F24F13/06—Outlets for directing or distributing air into rooms or spaces, e.g. ceiling air diffuser
- F24F2013/0616—Outlets that have intake openings
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F24—HEATING; RANGES; VENTILATING
- F24F—AIR-CONDITIONING; AIR-HUMIDIFICATION; VENTILATION; USE OF AIR CURRENTS FOR SCREENING
- F24F2110/00—Control inputs relating to air properties
- F24F2110/40—Pressure, e.g. wind pressure
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F24—HEATING; RANGES; VENTILATING
- F24F—AIR-CONDITIONING; AIR-HUMIDIFICATION; VENTILATION; USE OF AIR CURRENTS FOR SCREENING
- F24F2221/00—Details or features not otherwise provided for
- F24F2221/14—Details or features not otherwise provided for mounted on the ceiling
-
- Y—GENERAL TAGGING OF NEW TECHNOLOGICAL DEVELOPMENTS; GENERAL TAGGING OF CROSS-SECTIONAL TECHNOLOGIES SPANNING OVER SEVERAL SECTIONS OF THE IPC; TECHNICAL SUBJECTS COVERED BY FORMER USPC CROSS-REFERENCE ART COLLECTIONS [XRACs] AND DIGESTS
- Y02—TECHNOLOGIES OR APPLICATIONS FOR MITIGATION OR ADAPTATION AGAINST CLIMATE CHANGE
- Y02B—CLIMATE CHANGE MITIGATION TECHNOLOGIES RELATED TO BUILDINGS, e.g. HOUSING, HOUSE APPLIANCES OR RELATED END-USER APPLICATIONS
- Y02B30/00—Energy efficient heating, ventilation or air conditioning [HVAC]
- Y02B30/70—Efficient control or regulation technologies, e.g. for control of refrigerant flow, motor or heating
Landscapes
- Engineering & Computer Science (AREA)
- Chemical & Material Sciences (AREA)
- Combustion & Propulsion (AREA)
- Mechanical Engineering (AREA)
- General Engineering & Computer Science (AREA)
- Physics & Mathematics (AREA)
- Fluid Mechanics (AREA)
- Jet Pumps And Other Pumps (AREA)
- Duct Arrangements (AREA)
- Air-Flow Control Members (AREA)
Description
535 935 blandningskammaren till en fjärdedel enligt fysikaliska lagar. Det går alltså inte att minska energiförbruk- ningen hos centralfläkten genom att minska trycket eller luftflödet genom dysorna/hålen. 535 935 the mixing chamber to a quarter according to physical laws. It is therefore not possible to reduce the energy consumption of the central fan by reducing the pressure or air flow through the nozzles / holes.
Syftet med föreliggande uppfinning är att eliminera de nackdelar som finns med ovan nämnda konstruktioner, genom att bibehålla samma tryck och luftflöde genom varje öppen dysa/hål, då minst en av dem stängs på grund av minskat behov av ventilationsluft till utrymmet, vilket gör att undertrycket vid varje dysa/hål blir detsamma, varför undertrycket i bland- ningskammaren vid varje dysa/hål suger in rumsluften i blandningskammaren med god effektivitet samtidigt som centralfläkten minskar i varvtal och spar energi.The object of the present invention is to eliminate the disadvantages of the above-mentioned constructions, by maintaining the same pressure and air flow through each open nozzle / hole, as at least one of them is closed due to reduced need for ventilation air to the space, which means that the negative pressure at each nozzle / hole will be the same, which is why the negative pressure in the mixing chamber at each nozzle / hole sucks the room air into the mixing chamber with good efficiency at the same time as the central fan decreases in speed and saves energy.
Tack vare uppfinningen har man nu löst problemen med ovannämnda konstruktioner på ett enkelt och billigt sätt utan att tillföra extra fläktar och många andra rörliga delar, som kan gå sönder och samtidigt minskar energiförbrukningen. Uppfinningen hänför sig till ett ventilationsaggregat, som är tillverkat av bl. a. tunn plåt och plast och som förser utrymmen, t.ex. ett antal hotellrum, med ventilationsluft för att där erhålla en önskad luftmängd per tidsenhet och en önskad temperatur i utrymmena. Ventilationsluften kommer från en central- fläkt placerad utomhus och trycks in genom ett antal dysor/hål i ventilationsaggregatet med ett förutbestämt tryck på t.ex. 80 Pa, in i en blandningskammare i ventilationsaggregatet, som där skapar ett undertryck, som suger in rumsluft från utrymmet in i blandnings- kammaren genom en värmeväxlare ansluten till venti- lationsaggregatet. I blandningskammaren blandas rums- luften med ventilationsluften och uppvärms eller avkyls 535 935 med ett cirkulerande medium, t.ex. vatten i rör i värmeväxlaren. Den nu blandade luften trycks vidare därifrån in i utrymmet. Enligt uppfinningen trycks ventilationsluften genom ett önskat antal öppna lika stora dysor/hål, som genomströmmas av samma mängd ventilationsluft per styck och per tidsenhet. Dessa är anordnade i en vägg i ventilationsaggregatet som avskiljer blandningskammaren från en tryckkammare, till vilken ventilationsluften trycks in från ett venti- lationsrör sträckande sig från centralfläkten till tilluftshål in till tryckkammaren. Antalet dysor/hål, som är stängda eller är tillgängliga för tillförsel av ventilationsluft bestäms av hur stor mängd ventila- tionsluft, som för tillfället behövs till utrymmet. Då behovet är lägre än maximalt, stängs ett antal dysor/hål av från att passeras av ventilationsluften.Thanks to the invention, the problems with the above-mentioned constructions have now been solved in a simple and inexpensive manner without adding extra fans and many other moving parts, which can break and at the same time reduce the energy consumption. The invention relates to a ventilation unit, which is made of e.g. a. thin sheet metal and plastic and which provide spaces, e.g. a number of hotel rooms, with ventilation air to obtain a desired amount of air per unit of time and a desired temperature in the rooms. The ventilation air comes from a central fan located outdoors and is pushed in through a number of nozzles / holes in the ventilation unit with a predetermined pressure of e.g. 80 Pa, into a mixing chamber in the ventilation unit, which there creates a negative pressure, which sucks room air from the space into the mixing chamber through a heat exchanger connected to the ventilation unit. In the mixing chamber, the room air is mixed with the ventilation air and 535 935 is heated or cooled with a circulating medium, e.g. water in pipes in the heat exchanger. The now mixed air is pushed further from there into the space. According to the invention, the ventilation air is forced through a desired number of open equal nozzles / holes, which are flowed through by the same amount of ventilation air per piece and per unit of time. These are arranged in a wall of the ventilation unit which separates the mixing chamber from a pressure chamber, to which the ventilation air is forced in from a ventilation pipe extending from the central fan to the supply air hole into the pressure chamber. The number of nozzles / holes that are closed or available for the supply of ventilation air is determined by the amount of ventilation air that is currently needed for the space. When the need is lower than the maximum, a number of nozzles / holes are closed off from being passed by the ventilation air.
Ett färre antal än det maximala antalet dysor/ hål är då öppna, som passeras under samma tryck i tryck- kammaren, t.ex. 80 Pa och samma luftflöde per dysa/hål oavsett hur många dysor/hål som, är öppna. En tryckkännare eller trycksensor känner automatiskt trycket och anpassar detta till ett förutbestämt tryck, som kontinuerligt ligger på samma nivå vid dysorna/ hålen, varför centralfläkten behöver arbeta motsvarande mindre och därmed sparar energi, då ett färre antal dysor/hål är öppna.A smaller number than the maximum number of nozzles / holes are then open, which are passed under the same pressure in the pressure chamber, e.g. 80 Pa and the same air flow per nozzle / hole, regardless of how many nozzles / holes are open. A pressure sensor or pressure sensor automatically senses the pressure and adjusts this to a predetermined pressure, which is continuously at the same level at the nozzles / holes, so the central fan needs to work correspondingly less and thus saves energy, as a smaller number of nozzles / holes are open.
Uppfinningen beskrivs närmare nedan med hjälp av nâgra föredragna utföringsexempel, på vilka fig. 1 visar en genomlyst vy sedd uppifrån genom ett ventilationsaggregat, 535 935 fig. 2 visar ett vertikalt tvärsnitt genom ett ventilationsaggregat, fig. 3 visar ett vertikalt tvärsnitt genom en dysa/ hål pekande in i en blandningskammare, och fig. 4 visar ett vertikalt tvärsnitt genom en tryckkammare, sedd mot en vägg med dysor/hål.The invention is described in more detail below with the aid of some preferred embodiments, in which Fig. 1 shows a translucent view seen from above through a ventilation unit, Fig. 2 shows a vertical cross-section through a ventilation unit, Fig. 3 shows a vertical cross-section through a nozzle / holes pointing into a mixing chamber, and Fig. 4 shows a vertical cross-section through a pressure chamber, seen against a wall with nozzles / holes.
Såsom framgår av fig. 1 och 2 visas ett ventilations- aggregat 1, som förser ett utrymme 3 med ventila- tionsluft 2 utifrån via en centralfläkt 5. Venti- lationsluften 2 trycks in genom ett antal dysor/hål 4 med ett förutbestämt tryck i en blandningskammare 6 i ventilationsaggregatet 1 och där skapas då ett under- tryck, som suger in rumsluft 8 från utrymmet 3 in i blandningskammaren 6 genom en värmeväxlare 7, som blandas med ventilationsluften 2 till blandad luft 28, som trycks vidare in i utrymmet 3. Öppna dysor/hål 4 genomströmmas kontinuerligt av ventilationsluft 2 medan andra är stängda. En tryckkännare 22 känner automa- tiskt av trycket och anpassar detta att kontinuerligt ligga på samma nivå efter antalet öppna dysor/hål 4.As shown in Figs. 1 and 2, a ventilation unit 1 is shown, which supplies a space 3 with ventilation air 2 from the outside via a central fan 5. The ventilation air 2 is forced in through a number of nozzles / holes 4 with a predetermined pressure in a mixing chamber 6 in the ventilation unit 1 and there a negative pressure is then created, which sucks room air 8 from the space 3 into the mixing chamber 6 through a heat exchanger 7, which is mixed with the ventilation air 2 to mixed air 28, which is pushed further into the space 3. Open nozzles / holes 4 are continuously flowed through by ventilation air 2 while others are closed. A pressure sensor 22 automatically senses the pressure and adjusts this to be continuously at the same level according to the number of open nozzles / holes 4.
Dessa är anordnade i en vägg 9, som avskiljer bland- ningskammaren 6 från en tryckkammare 10, till vilken ventilationsluften 2 trycks in från minst ett ven- tilationsrör 12 från centralfläkten 5 till till- luftshâl ll i tryckkammaren 10. Ventilationsaggregatet l är format som en låda 29. Dysorna/hålen 4 är anordnade utefter en horisontell linje 25 (fig.4) i väggen 9 ett stycke från varandra och pekar tvärs väggen 9 in mot blandningskammaren 6. Tryckkammares 10 innertak V23 är anordnat mot utrymmets 3 tak 24. 535 935 Värmeväxlaren 7 är anordnad under blandningskammaren 6, för att där suga in rumsluften 8 genom värmeväxlaren 7 från utrymmets 3 övre del där rumsluften 8 är som varmast. Vid en föredragen utföringsform av upp- finningen är tryckkammaren 10 uppdelad med en mellan- vägg 21 till två mindre tryckkammare 14 med var sin tryckkännare 22, med var sitt tilluftshål 11, där ven- tilationsluften 2 trycks in genom var sitt venti- lationsrör 12, som uppvisar var sitt spjäll 13, för att öppna eller stänga genomströmning av ventilations- luften 2. Dysorna/hålen 4 med stängt spjäll 13 genomströmmas då ej. Dysorna/hålen 4 med öppet spjäll 13 genomströmmas däremot. I ytterligare en variant av uppfinningen är lådan 29 ca 1000x1000x20O mm. Väggen 9 är då rak och uppvisar fem dysor/hål 4. De två mindre tryckkamrarna 14 uppvisar en bredd i ventilations- luftens 2 flödesriktning 17 på ca 170 mm. Den ena, mindre tryckkammaren 14 uppvisar två dysor/hål 4 och den andra tre dysor/hål 4. Med spjällens 13 hjälp, är det möjligt att välja två, tre eller fem öppna dysor/ hål 4. Naturligtvis kan uppfinningen också tillämpas om dysorna/hålen 4 är helt öppnings- och stängningsbara med hjälp av manövrerbara element, såsom t.ex. en lucka för att efter önskemål, via ett utanför utrymmet 3 manövrerbart reglage, styra elementet manuellt att vara öppet eller stängt eller så kan elementen styras av en elektrisk motor, som manövreras elektriskt med kontakt- reglage.These are arranged in a wall 9, which separates the mixing chamber 6 from a pressure chamber 10, to which the ventilation air 2 is forced in from at least one ventilation pipe 12 from the central fan 5 to the supply air hole 11 in the pressure chamber 10. The ventilation unit 1 is formed as a box 29. The nozzles / holes 4 are arranged along a horizontal line 25 (Fig. 4) in the wall 9 some distance apart and point across the wall 9 towards the mixing chamber 6. The ceiling V23 of the pressure chamber 10 is arranged against the roof 24 of the space 3. 535 935 The heat exchanger 7 is arranged below the mixing chamber 6, in order to suck in the room air 8 there through the heat exchanger 7 from the upper part of the space 3 where the room air 8 is warmest. In a preferred embodiment of the invention, the pressure chamber 10 is divided by a partition wall 21 into two smaller pressure chambers 14, each with a pressure sensor 22, each with a supply air hole 11, where the ventilation air 2 is forced in through each ventilation pipe 12, which each have their own damper 13, in order to open or close the flow of the ventilation air 2. The nozzles / holes 4 with closed damper 13 are then not flowed through. The nozzles / holes 4 with open damper 13, on the other hand, flow through. In another variant of the invention, the box 29 is approximately 1000x1000x20O mm. The wall 9 is then straight and has five nozzles / holes 4. The two smaller pressure chambers 14 have a width in the flow direction 17 of the ventilation air 2 of approx. 170 mm. One, smaller pressure chamber 14 has two nozzles / holes 4 and the other three nozzles / holes 4. With the help of the dampers 13, it is possible to select two, three or five open nozzles / holes 4. Of course, the invention can also be applied if the nozzles / the holes 4 can be fully opened and closed by means of manoeuvrable elements, such as e.g. a hatch to, if desired, via a controllable control unit outside the space 3, manually control the element to be open or closed, or the elements can be controlled by an electric motor, which is electrically operated with contact controls.
Såsom framgår av fig. 3 är dysorna/hålen 4 formade som en ihålig kon 16 utan spets, vars längd är ca 20 mm, vars mantelyta uppvisar en tjocklek på ca 0,5-2 mm och som har en rund öppning i varje ände igenom vilka ventilationsluften 2 strömmar i en flödesriktning 17. 535 935 Konen 16 uppvisar en smalare rund öppning 18 på ca 25 mmzs diameter, som är vänd in i blandningskammaren 6 och en bredare rund öppning 19 på ca 30 mmzs diameter, igenom vilken ventilationsluften 2 strömmar in, som är tätt ansluten i ett lika stort hål i väggen 9.As can be seen from Fig. 3, the nozzles / holes 4 are formed as a hollow cone 16 without a tip, the length of which is about 20 mm, the circumferential surface of which has a thickness of about 0.5-2 mm and which has a round opening at each end through which the ventilation air 2 flows in a flow direction 17. 535 935 The cone 16 has a narrower round opening 18 of about 25 mmzs diameter, which is turned into the mixing chamber 6 and a wider round opening 19 of about 30 mmzs diameter, through which the ventilation air 2 flows in. , which is tightly connected in an equally large hole in the wall 9.
Undertryck etableras vid den smalare diametern 18, där ventilationsluften 2 ökar sin flödeshastighet och divergerar in i blandningskammaren 6 med ca 10-30 graders spridning runt om konens 16 centrumlinje 15, som är vinklad ca 90 grader mot väggen 9, som är vinklad 90 grader mot innertaket 23. Luftflödet genom varje kon 16 är ca 4 liter/sek. Konen 16 uppvisar en rundad radie 20 på sin insida, vid sin anslutning mot väggen 9 för att underlätta luftflödet genom konen 16 in i blandningskammaren 6, där den strömmar vidare ut genom minst en öppning 30, som är formad som ett raster, som ger ett litet luftmotstånd och är anordnat i làdans 29 främre gavel 31, pekande in i utrymmet 3 i en riktning parallell med taket 24 för att erhålla ett jämt fördelat tryck mot hela öppningen 30, som tystar ner den blandade luftens 28 utströmning genom öppningen .Negative pressure is established at the narrower diameter 18, where the ventilation air 2 increases its flow rate and diverges into the mixing chamber 6 by about 10-30 degrees spread around the center line 15 of the cone 16, which is angled about 90 degrees to the wall 9, which is angled 90 degrees to the ceiling 23. The air flow through each cone 16 is about 4 liters / sec. The cone 16 has a rounded radius 20 on its inside, at its connection to the wall 9 to facilitate the air flow through the cone 16 into the mixing chamber 6, where it flows further out through at least one opening 30, which is formed as a grid, which gives a low air resistance and is arranged in the front end 31 of the drawer 29, pointing into the space 3 in a direction parallel to the roof 24 to obtain an evenly distributed pressure against the entire opening 30, which silences the outflow of the mixed air 28 through the opening.
Såsom framgår av fig. 4 delar mellanväggen 21 upp tryckkammaren 10 genom att avgränsa varannan dysa/hål 4 till en första mindre tryckkammare 26, som är vänd uppàt mot innertaket 23 och varannan dysa/hål 4 avgränsas neråt mot utrymmet 3 till en andra mindre tryckkammare 27, varvid vid avstängningen av spjället 13, stänger varannan dysa/hål 4, vilken ventilations- luft 2 då fördelas jämt över hela blandningskammaren 6.As shown in Fig. 4, the partition wall 21 divides the pressure chamber 10 by delimiting every second nozzle / hole 4 to a first smaller pressure chamber 26, which faces upwards towards the ceiling 23 and every second nozzle / hole 4 is delimited downwards towards the space 3 to a second smaller pressure chamber 27, whereby when closing the damper 13, every other nozzle / hole 4 closes, which ventilation air 2 is then distributed evenly over the entire mixing chamber 6.
Claims (10)
Priority Applications (2)
| Application Number | Priority Date | Filing Date | Title |
|---|---|---|---|
| SE1100319A SE535935C2 (en) | 2011-04-27 | 2011-04-27 | Device at a ventilation unit |
| PCT/SE2012/000058 WO2012148339A1 (en) | 2011-04-27 | 2012-04-26 | Improvements in or relating to a ventilation unit |
Applications Claiming Priority (1)
| Application Number | Priority Date | Filing Date | Title |
|---|---|---|---|
| SE1100319A SE535935C2 (en) | 2011-04-27 | 2011-04-27 | Device at a ventilation unit |
Publications (2)
| Publication Number | Publication Date |
|---|---|
| SE1100319A1 SE1100319A1 (en) | 2012-10-28 |
| SE535935C2 true SE535935C2 (en) | 2013-02-26 |
Family
ID=47072604
Family Applications (1)
| Application Number | Title | Priority Date | Filing Date |
|---|---|---|---|
| SE1100319A SE535935C2 (en) | 2011-04-27 | 2011-04-27 | Device at a ventilation unit |
Country Status (2)
| Country | Link |
|---|---|
| SE (1) | SE535935C2 (en) |
| WO (1) | WO2012148339A1 (en) |
Family Cites Families (6)
| Publication number | Priority date | Publication date | Assignee | Title |
|---|---|---|---|---|
| US3186327A (en) * | 1963-02-28 | 1965-06-01 | Worthington Corp | Induction unit for air conditioning systems |
| DE19921463A1 (en) * | 1999-03-11 | 2000-09-14 | Adam Bernhardt | Process for tempering a hall and device for carrying out the process |
| US6213867B1 (en) * | 2000-01-12 | 2001-04-10 | Air Handling Engineering Ltd. | Venturi type air distribution system |
| FI122286B (en) * | 2006-01-16 | 2011-11-15 | Halton Oy | Supply air device and method for controlling the amount of air flow |
| FI122289B (en) * | 2008-07-24 | 2011-11-15 | Halton Oy | The air exchange system and the method of air exchange |
| NL2002015C (en) * | 2008-09-24 | 2010-03-25 | Inteco B V | CROSS FLOW INDUCTION CEILING CONVECTOR. |
-
2011
- 2011-04-27 SE SE1100319A patent/SE535935C2/en not_active IP Right Cessation
-
2012
- 2012-04-26 WO PCT/SE2012/000058 patent/WO2012148339A1/en not_active Ceased
Also Published As
| Publication number | Publication date |
|---|---|
| SE1100319A1 (en) | 2012-10-28 |
| WO2012148339A1 (en) | 2012-11-01 |
Similar Documents
| Publication | Publication Date | Title |
|---|---|---|
| KR101628317B1 (en) | Heat recovery ventilators | |
| CN106642310B (en) | Air conditioner and control method thereof | |
| EP2518418B1 (en) | Fan convector | |
| US10477867B2 (en) | Oven appliance with air curtain | |
| JP2016180533A (en) | Intake/exhaust unit and double skin system using the same | |
| SE0950029A1 (en) | Induction apparatus for combining air flows | |
| CN204555003U (en) | Split floor type air conditioner | |
| SE0850182A1 (en) | A ventilation device | |
| JP5102579B2 (en) | Air conditioning system | |
| CN105387588B (en) | Air duct assembly and air conditioner with same | |
| CN110785057A (en) | Integrated unit cabinet with vertical air duct | |
| SE535935C2 (en) | Device at a ventilation unit | |
| AU2011358211B2 (en) | Method for operating a ventilation system with a mixing chamber | |
| SE534485C2 (en) | A ventilation device | |
| CN105588233B (en) | A kind of air-conditioner outdoor unit air exhausting structure and air-conditioner outdoor unit | |
| CN106288275B (en) | Air conditioner | |
| SE0602705L (en) | Drying cabinet | |
| DE10022354C1 (en) | Heat recovery and ventilation device for vertical cavities in external walls, comprises casing with separate inlet and exit channels containing heating pipes and fans | |
| CN110878966B (en) | Variable position asymmetric air guide structure and air conditioner | |
| CN207160904U (en) | A kind of temperature adjusting window and building | |
| KR20130059550A (en) | Reverse-return type ventilator | |
| CN105698355A (en) | Air conditioner air guiding device and air conditioner | |
| CN201149331Y (en) | Hot air blower group structure | |
| CN202494197U (en) | Temperature control annular jet flow air port | |
| CN213656911U (en) | Pipeline type air heating ventilator |
Legal Events
| Date | Code | Title | Description |
|---|---|---|---|
| NUG | Patent has lapsed |