DX-8348 cone-shapeCalorimeter
Ⅰ、E standard:met the standard required testing method of GB/T16172-2007《the testing method for building materials heat release speed》andISO5660-1:2002《Testmethodforheatreleaserateofbuildingmaterials》.
Ⅱ、range of using:caculate the oxygen consumption through the oxygen concentrations in airflow of combuston produts, as well as the heat release speed of the combustion produts whiling aflame . The heat release speed of material is also an important parametric for material combustion capability,it is quiet important to measure the heat release speed of aflame material accurately for forecasting damage by fire disaster and the process for prevent flame retardant.
Ⅲ、working
conditions:
1、working
envirenment tempreture:0℃-50℃
2、working
envirenment humidity<80%
3、power supply:380V±50%,50Hz±2%
Ⅳ、main
capability prrameter:
1、radiate
conic:heating
capacity:5Kv,radiate
strength:100Kw/m2,allocate three thermocouple
mesure temperature.
2、exhaust
system:made of centrifuge
air-blower,exhaust fume collecting hood, blower’s
in-breath and out-breath pipe , and the orifice
meter.
The
maxmum placement amount of the sample box:up to 100mm*100mm*50mm。
3、exhaust
capactiy:0.012m3/s~0.035m3/s(adjustable)
4、timing
amount resolution:1Saverages error <1s/n
5、oxygen Analyzer:Siemens paramagnetic oxygen
analyzer,02measure
range:0-25%
6、e
with sampling pump and the smoke dust filter
7、gas
flow use imported high flow
controller
8、ignition
voltage:220V,bipolar
electrode,insure the safty of
testing.
9、exhaust
smoke flow:smoke exhaust fan adopts frequency
conversion control,it can achive the exhaust smoke
range at 0.012m3/s~0.035m3/sautomaticly。
10、control system:use Detectioncontrol
system and ZWH4500gatheringcontrol
card.
,it can achive Automatic Digital
Data Ac, processing, data save and export measure
report.